How many #14 THHN fit in 1-1/2" Liquidtight?
8114 AWG THHN/THWN-2 wires in 1-1/2" Liquidtight flexible metal conduit (LFMC)
1.981 sq in × 40 % = 0.7924 sq in allowed. ÷ 0.0097 sq in per wire = 81.69, so 81.
This pull in numbers
- 81 wires fill
- 39.7 % of 1-1/2" Liquidtight
- Limit for three or more
- 40 %
- For 82 or more
- 2" Liquidtight, up to 134
- Pipe to wire diameter
- 14.31 to 1
- In THW insulation
- 57 fit
- In XHHW-2 insulation
- 57 fit
Before you pull 81
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 81 is the total, not the hots.
- Derating. If all 81 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #14 THHN at 25 A in the 90 °C column becomes 8.8 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#14 THHN in other 1-1/2" conduit
| Conduit | Inside area | Most #14 THHN |
|---|---|---|
| Electrical metallic tubing | 2.036 | 84 |
| Intermediate metal conduit | 2.225 | 91 |
| Rigid metal conduit (RMC, GRC) | 2.071 | 85 |
| Rigid PVC conduit, Schedule 40 | 1.986 | 82 |
| Rigid PVC conduit, Schedule 80 | 1.711 | 70 |
| Flexible metal conduit (FMC, Greenfield) | 1.858 | 76 |
| Liquidtight flexible metal conduit (LFMC) | 1.981 | 81 |
| Electrical nonmetallic tubing (smurf tube) | 1.986 | 82 |
#14 THHN in other Liquidtight sizes
Other wire sizes in 1-1/2" Liquidtight
#14: 81#12: 59#10: 37#8: 21#6: 15#4: 9#3: 8#2: 7#1: 5#1/0: 4#2/0: 3#3/0: 3#4/0: 1250 kcmil: 1300 kcmil: 1350 kcmil: 1500 kcmil: 1