ConduitCount

How many #6 THHN fit in 1/2" PVC Sch 40?

16 AWG THHN/THWN-2 wires in 1/2" Rigid PVC conduit, Schedule 40

0.285 sq in × 53 % = 0.1510 sq in allowed. ÷ 0.0507 sq in per wire = 2.98.

1 #6 THHN in 1/2" PVC Sch 40, drawn to scale

This pull in numbers

1 wires fill
17.8 % of 1/2" PVC Sch 40
Limit for one
53 %
For 2 or more
3/4" PVC Sch 40, up to 4
Pipe to wire diameter
2.37 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#6 THHN in other 1/2" conduit

#6 THHN in other PVC Sch 40 sizes

Other wire sizes in 1/2" PVC Sch 40

Charts