ConduitCount

How many #6 THHN fit in 2-1/2" PVC Sch 40?

376 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 40

4.695 sq in × 40 % = 1.8780 sq in allowed. ÷ 0.0507 sq in per wire = 37.04, so 37.

37 #6 THHN in 2-1/2" PVC Sch 40, drawn to scale

This pull in numbers

37 wires fill
40.0 % of 2-1/2" PVC Sch 40
Limit for three or more
40 %
For 38 or more
3" PVC Sch 40, up to 57
Pipe to wire diameter
9.63 to 1
In THW insulation
26 fit
In XHHW-2 insulation
32 fit

Before you pull 37

#6 THHN in other 2-1/2" conduit

#6 THHN in other PVC Sch 40 sizes

Other wire sizes in 2-1/2" PVC Sch 40

Charts