How many #6 THHN fit in 4" PVC Sch 40?
996 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 40
12.554 sq in × 40 % = 5.0216 sq in allowed. ÷ 0.0507 sq in per wire = 99.05, so 99.
This pull in numbers
- 99 wires fill
- 40.0 % of 4" PVC Sch 40
- Limit for three or more
- 40 %
- For 100 or more
- 5" PVC Sch 40, up to 156
- Pipe to wire diameter
- 15.74 to 1
- In THW insulation
- 69 fit
- In XHHW-2 insulation
- 85 fit
Before you pull 99
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 99 is the total, not the hots.
- Derating. If all 99 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #6 THHN at 75 A in the 90 °C column becomes 26.3 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#6 THHN in other 4" conduit
| Conduit | Inside area | Most #6 THHN |
|---|---|---|
| Electrical metallic tubing | 14.753 | 116 |
| Intermediate metal conduit | 13.631 | 107 |
| Rigid metal conduit (RMC, GRC) | 12.882 | 101 |
| Rigid PVC conduit, Schedule 40 | 12.554 | 99 |
| Rigid PVC conduit, Schedule 80 | 11.258 | 89 |
| Flexible metal conduit (FMC, Greenfield) | 12.566 | 99 |
| Liquidtight flexible metal conduit (LFMC) | 12.692 | 100 |
#6 THHN in other PVC Sch 40 sizes
Other wire sizes in 4" PVC Sch 40
#8: 137#6: 99#4: 61#3: 51#2: 43#1: 32#1/0: 27#2/0: 22#3/0: 18#4/0: 15250 kcmil: 12300 kcmil: 11350 kcmil: 9500 kcmil: 7