ConduitCount

How many #6 THHN fit in 4" PVC Sch 40?

996 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 40

12.554 sq in × 40 % = 5.0216 sq in allowed. ÷ 0.0507 sq in per wire = 99.05, so 99.

99 #6 THHN in 4" PVC Sch 40, drawn to scale

This pull in numbers

99 wires fill
40.0 % of 4" PVC Sch 40
Limit for three or more
40 %
For 100 or more
5" PVC Sch 40, up to 156
Pipe to wire diameter
15.74 to 1
In THW insulation
69 fit
In XHHW-2 insulation
85 fit

Before you pull 99

#6 THHN in other 4" conduit

#6 THHN in other PVC Sch 40 sizes

Other wire sizes in 4" PVC Sch 40

Charts