ConduitCount

How many #6 THHN fit in 3-1/2" PVC Sch 40?

776 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.0507 sq in per wire = 76.82, which Note 7 rounds up to 77 because the decimal is 0.8 or more.

77 #6 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

77 wires fill
40.1 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 78 or more
4" PVC Sch 40, up to 99
Pipe to wire diameter
13.86 to 1
In THW insulation
53 fit
In XHHW-2 insulation
66 fit

Before you pull 77

#6 THHN in other 3-1/2" conduit

#6 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40

Charts