How many #8 THHN fit in 1/2" EMT?

38 AWG THHN/THWN-2 wires in 1/2" Electrical metallic tubing

0.304 sq in × 40 % = 0.1216 sq in allowed. ÷ 0.0366 sq in per wire = 3.32, so 3.

3 #8 THHN in 1/2" EMT, drawn to scale

This pull in numbers

3 wires fill
36.1 % of 1/2" EMT
Limit for three or more
40 %
For 4 or more
3/4" EMT, up to 6
Pipe to wire diameter
2.88 to 1
In THW insulation
2 fit
In XHHW-2 insulation
2 fit

The pipe is 2.88 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.