How many #8 THHN fit in 1" EMT?

98 AWG THHN/THWN-2 wires in 1" Electrical metallic tubing

0.864 sq in × 40 % = 0.3456 sq in allowed. ÷ 0.0366 sq in per wire = 9.44, so 9.

9 #8 THHN in 1" EMT, drawn to scale

This pull in numbers

9 wires fill
38.1 % of 1" EMT
Limit for three or more
40 %
For 10 or more
1-1/4" EMT, up to 16
Pipe to wire diameter
4.86 to 1
In THW insulation
8 fit
In XHHW-2 insulation
8 fit

Before you pull 9

#8 THHN in other 1" conduit

#8 THHN in other EMT sizes

Other wire sizes in 1" EMT