510 AWG THHN/THWN-2 wires in 1/2" Electrical metallic tubing

0.304 sq in × 40 % = 0.1216 sq in allowed. ÷ 0.0211 sq in per wire = 5.76, so 5.

5 #10 THHN in 1/2" EMT, drawn to scale

This pull in numbers

5 wires fill
34.7 % of 1/2" EMT
Limit for three or more
40 %
For 6 or more
3/4" EMT, up to 10
Pipe to wire diameter
3.79 to 1
In THW insulation
5 fit
In XHHW-2 insulation
5 fit

Before you pull 5

#10 THHN in other 1/2" conduit

#10 THHN in other EMT sizes