How many #8 THHN fit in 1/2" IMC?

38 AWG THHN/THWN-2 wires in 1/2" Intermediate metal conduit

0.342 sq in × 40 % = 0.1368 sq in allowed. ÷ 0.0366 sq in per wire = 3.74, so 3.

3 #8 THHN in 1/2" IMC, drawn to scale

This pull in numbers

3 wires fill
32.1 % of 1/2" IMC
Limit for three or more
40 %
For 4 or more
3/4" IMC, up to 6
Pipe to wire diameter
3.06 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 3.06 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.