ConduitCount

How many 400 kcmil THHN/THWN-2 fit in conduit

400 kcmil THHN/THWN-2 is about 0.864 in across and 0.5863 sq in with its insulation (Chapter 9, Table 5). This is the most of it each conduit may hold, all the same size.

Trade sizeEMTIMCRigidPVC Sch 40PVC Sch 80FlexLiquidtightENT
1-1/4"11111111
1-1/2"11111111
2"11111111
2-1/2"4333333
3"6555455
3-1/2"8776666
4"10988788
5"131312
6"201917

Empty cells: that type isn't made in that size.

Other sizes of THHN/THWN-2

The same size in other insulation