ConduitCount

How many #14 THHN fit in 1/2" PVC Sch 80?

914 AWG THHN/THWN-2 wires in 1/2" Rigid PVC conduit, Schedule 80

0.217 sq in × 40 % = 0.0868 sq in allowed. ÷ 0.0097 sq in per wire = 8.95, which Note 7 rounds up to 9 because the decimal is 0.8 or more.

9 #14 THHN in 1/2" PVC Sch 80, drawn to scale

This pull in numbers

9 wires fill
40.2 % of 1/2" PVC Sch 80
Limit for three or more
40 %
For 10 or more
3/4" PVC Sch 80, up to 17
Pipe to wire diameter
4.74 to 1
In THW insulation
6 fit
In XHHW-2 insulation
6 fit

Before you pull 9

#14 THHN in other 1/2" conduit

#14 THHN in other PVC Sch 80 sizes

Other wire sizes in 1/2" PVC Sch 80

Charts