How many #14 THHN fit in 1/2" PVC Sch 80?
914 AWG THHN/THWN-2 wires in 1/2" Rigid PVC conduit, Schedule 80
0.217 sq in × 40 % = 0.0868 sq in allowed. ÷ 0.0097 sq in per wire = 8.95, which Note 7 rounds up to 9 because the decimal is 0.8 or more.
This pull in numbers
- 9 wires fill
- 40.2 % of 1/2" PVC Sch 80
- Limit for three or more
- 40 %
- For 10 or more
- 3/4" PVC Sch 80, up to 17
- Pipe to wire diameter
- 4.74 to 1
- In THW insulation
- 6 fit
- In XHHW-2 insulation
- 6 fit
Before you pull 9
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 9 is the total, not the hots.
- Derating. If all 9 were current-carrying, each would be adjusted to 70 % of its ampacity (Table 310.15(C)(1)): a #14 THHN at 25 A in the 90 °C column becomes 17.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#14 THHN in other 1/2" conduit
| Conduit | Inside area | Most #14 THHN |
|---|---|---|
| Electrical metallic tubing | 0.304 | 12 |
| Intermediate metal conduit | 0.342 | 14 |
| Rigid metal conduit (RMC, GRC) | 0.314 | 13 |
| Rigid PVC conduit, Schedule 40 | 0.285 | 11 |
| Rigid PVC conduit, Schedule 80 | 0.217 | 9 |
| Flexible metal conduit (FMC, Greenfield) | 0.317 | 13 |
| Liquidtight flexible metal conduit (LFMC) | 0.314 | 13 |
| Electrical nonmetallic tubing (smurf tube) | 0.285 | 11 |