ConduitCount

How many #10 THHN fit in 1/2" PVC Sch 80?

410 AWG THHN/THWN-2 wires in 1/2" Rigid PVC conduit, Schedule 80

0.217 sq in × 40 % = 0.0868 sq in allowed. ÷ 0.0211 sq in per wire = 4.11, so 4.

4 #10 THHN in 1/2" PVC Sch 80, drawn to scale

This pull in numbers

4 wires fill
38.9 % of 1/2" PVC Sch 80
Limit for three or more
40 %
For 5 or more
3/4" PVC Sch 80, up to 7
Pipe to wire diameter
3.21 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

Before you pull 4

#10 THHN in other 1/2" conduit

#10 THHN in other PVC Sch 80 sizes

Other wire sizes in 1/2" PVC Sch 80

Charts