ConduitCount

How many #14 THHN fit in 3/8" Liquidtight?

814 AWG THHN/THWN-2 wires in 3/8" Liquidtight flexible metal conduit (LFMC)

0.192 sq in × 40 % = 0.0768 sq in allowed. ÷ 0.0097 sq in per wire = 7.92, which Note 7 rounds up to 8 because the decimal is 0.8 or more.

8 #14 THHN in 3/8" Liquidtight, drawn to scale

This pull in numbers

8 wires fill
40.4 % of 3/8" Liquidtight
Limit for three or more
40 %
For 9 or more
1/2" Liquidtight, up to 13
Pipe to wire diameter
4.45 to 1
In THW insulation
5 fit
In XHHW-2 insulation
5 fit

Before you pull 8

#14 THHN in other 3/8" conduit

ConduitInside areaMost #14 THHN
Flexible metal conduit (FMC, Greenfield)0.1164
Liquidtight flexible metal conduit (LFMC)0.1928

#14 THHN in other Liquidtight sizes

Other wire sizes in 3/8" Liquidtight