310 AWG THHN/THWN-2 wires in 3/8" Liquidtight flexible metal conduit (LFMC)

0.192 sq in × 40 % = 0.0768 sq in allowed. ÷ 0.0211 sq in per wire = 3.64, so 3.

3 #10 THHN in 3/8" Liquidtight, drawn to scale

This pull in numbers

3 wires fill
33.0 % of 3/8" Liquidtight
Limit for three or more
40 %
For 4 or more
1/2" Liquidtight, up to 6
Pipe to wire diameter
3.01 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 3.01 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.