ConduitCount

How many #2/0 THHN fit in 3" Liquidtight?

132/0 AWG THHN/THWN-2 wires in 3" Liquidtight flexible metal conduit (LFMC)

7.475 sq in × 40 % = 2.9900 sq in allowed. ÷ 0.2223 sq in per wire = 13.45, so 13.

13 #2/0 THHN in 3" Liquidtight, drawn to scale

This pull in numbers

13 wires fill
38.7 % of 3" Liquidtight
Limit for three or more
40 %
For 14 or more
3-1/2" Liquidtight, up to 17
Pipe to wire diameter
5.80 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 13

#2/0 THHN in other 3" conduit

ConduitInside areaMost #2/0 THHN
Electrical metallic tubing8.84616
Intermediate metal conduit7.92214
Rigid metal conduit (RMC, GRC)7.49913
Rigid PVC conduit, Schedule 407.26813
Rigid PVC conduit, Schedule 806.44211
Flexible metal conduit (FMC, Greenfield)7.06912
Liquidtight flexible metal conduit (LFMC)7.47513

#2/0 THHN in other Liquidtight sizes

Other wire sizes in 3" Liquidtight

Charts