262 AWG THHN/THWN-2 wires in 3" Liquidtight flexible metal conduit (LFMC)

7.475 sq in × 40 % = 2.9900 sq in allowed. ÷ 0.1158 sq in per wire = 25.82, which Note 7 rounds up to 26 because the decimal is 0.8 or more.

26 #2 THHN in 3" Liquidtight, drawn to scale

This pull in numbers

26 wires fill
40.3 % of 3" Liquidtight
Limit for three or more
40 %
For 27 or more
3-1/2" Liquidtight, up to 33
Pipe to wire diameter
8.03 to 1
In THW insulation
22 fit
In XHHW-2 insulation
26 fit

Before you pull 26

#2 THHN in other 3" conduit

ConduitInside areaMost #2 THHN
Electrical metallic tubing8.84630
Intermediate metal conduit7.92227
Rigid metal conduit (RMC, GRC)7.49926
Rigid PVC conduit, Schedule 407.26825
Rigid PVC conduit, Schedule 806.44222
Flexible metal conduit (FMC, Greenfield)7.06924
Liquidtight flexible metal conduit (LFMC)7.47526