How many #4/0 THHN fit in 3" Liquidtight?
94/0 AWG THHN/THWN-2 wires in 3" Liquidtight flexible metal conduit (LFMC)
7.475 sq in × 40 % = 2.9900 sq in allowed. ÷ 0.3237 sq in per wire = 9.24, so 9.
This pull in numbers
- 9 wires fill
- 39.0 % of 3" Liquidtight
- Limit for three or more
- 40 %
- For 10 or more
- 3-1/2" Liquidtight, up to 12
- Pipe to wire diameter
- 4.81 to 1
- In THW insulation
- 8 fit
- In XHHW-2 insulation
- 9 fit
Before you pull 9
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 9 is the total, not the hots.
- Derating. If all 9 were current-carrying, each would be adjusted to 70 % of its ampacity (Table 310.15(C)(1)): a #4/0 THHN at 260 A in the 90 °C column becomes 182 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#4/0 THHN in other 3" conduit
| Conduit | Inside area | Most #4/0 THHN |
|---|---|---|
| Electrical metallic tubing | 8.846 | 11 |
| Intermediate metal conduit | 7.922 | 9 |
| Rigid metal conduit (RMC, GRC) | 7.499 | 9 |
| Rigid PVC conduit, Schedule 40 | 7.268 | 9 |
| Rigid PVC conduit, Schedule 80 | 6.442 | 8 |
| Flexible metal conduit (FMC, Greenfield) | 7.069 | 8 |
| Liquidtight flexible metal conduit (LFMC) | 7.475 | 9 |
#4/0 THHN in other Liquidtight sizes
Other wire sizes in 3" Liquidtight
#10: 141#8: 81#6: 59#4: 36#3: 30#2: 26#1: 19#1/0: 16#2/0: 13#3/0: 11#4/0: 9250 kcmil: 7300 kcmil: 6350 kcmil: 5500 kcmil: 4