ConduitCount

How many #10 THHN fit in 3" Liquidtight?

14110 AWG THHN/THWN-2 wires in 3" Liquidtight flexible metal conduit (LFMC)

7.475 sq in × 40 % = 2.9900 sq in allowed. ÷ 0.0211 sq in per wire = 141.71, so 141.

141 #10 THHN in 3" Liquidtight, drawn to scale

This pull in numbers

141 wires fill
39.8 % of 3" Liquidtight
Limit for three or more
40 %
For 142 or more
3-1/2" Liquidtight, up to 184
Pipe to wire diameter
18.81 to 1
In THW insulation
123 fit
In XHHW-2 insulation
123 fit

Before you pull 141

#10 THHN in other 3" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing8.846167
Intermediate metal conduit7.922150
Rigid metal conduit (RMC, GRC)7.499142
Rigid PVC conduit, Schedule 407.268137
Rigid PVC conduit, Schedule 806.442122
Flexible metal conduit (FMC, Greenfield)7.069134
Liquidtight flexible metal conduit (LFMC)7.475141

#10 THHN in other Liquidtight sizes

Other wire sizes in 3" Liquidtight

Charts