ConduitCount

How many #3 THHN fit in 3" Liquidtight?

303 AWG THHN/THWN-2 wires in 3" Liquidtight flexible metal conduit (LFMC)

7.475 sq in × 40 % = 2.9900 sq in allowed. ÷ 0.0973 sq in per wire = 30.73, so 30.

30 #3 THHN in 3" Liquidtight, drawn to scale

This pull in numbers

30 wires fill
39.1 % of 3" Liquidtight
Limit for three or more
40 %
For 31 or more
3-1/2" Liquidtight, up to 40
Pipe to wire diameter
8.76 to 1
In THW insulation
26 fit
In XHHW-2 insulation
31 fit

Before you pull 30

#3 THHN in other 3" conduit

ConduitInside areaMost #3 THHN
Electrical metallic tubing8.84636
Intermediate metal conduit7.92232
Rigid metal conduit (RMC, GRC)7.49931
Rigid PVC conduit, Schedule 407.26830
Rigid PVC conduit, Schedule 806.44226
Flexible metal conduit (FMC, Greenfield)7.06929
Liquidtight flexible metal conduit (LFMC)7.47530

#3 THHN in other Liquidtight sizes

Other wire sizes in 3" Liquidtight

Charts