ConduitCount

How many #4/0 THHN fit in 2" ENT?

44/0 AWG THHN/THWN-2 wires in 2" Electrical nonmetallic tubing (smurf tube)

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.3237 sq in per wire = 4.07, so 4.

4 #4/0 THHN in 2" ENT, drawn to scale

This pull in numbers

4 wires fill
39.3 % of 2" ENT
Limit for three or more
40 %
For 5 or more
no bigger ENT
Pipe to wire diameter
3.19 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

The pipe is 3.19 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 4

#4/0 THHN in other 2" conduit

#4/0 THHN in other ENT sizes

Other wire sizes in 2" ENT

Charts