ConduitCount

How many #6 THHN fit in 1" Flex?

66 AWG THHN/THWN-2 wires in 1" Flexible metal conduit (FMC, Greenfield)

0.817 sq in × 40 % = 0.3268 sq in allowed. ÷ 0.0507 sq in per wire = 6.45, so 6.

6 #6 THHN in 1" Flex, drawn to scale

This pull in numbers

6 wires fill
37.2 % of 1" Flex
Limit for three or more
40 %
For 7 or more
1-1/4" Flex, up to 10
Pipe to wire diameter
4.02 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 6

#6 THHN in other 1" conduit

#6 THHN in other Flex sizes

Other wire sizes in 1" Flex

Charts