ConduitCount

How many #6 THHN fit in 2" Flex?

256 AWG THHN/THWN-2 wires in 2" Flexible metal conduit (FMC, Greenfield)

3.269 sq in × 40 % = 1.3076 sq in allowed. ÷ 0.0507 sq in per wire = 25.79, so 25.

25 #6 THHN in 2" Flex, drawn to scale

This pull in numbers

25 wires fill
38.8 % of 2" Flex
Limit for three or more
40 %
For 26 or more
2-1/2" Flex, up to 38
Pipe to wire diameter
8.03 to 1
In THW insulation
18 fit
In XHHW-2 insulation
22 fit

Before you pull 25

#6 THHN in other 2" conduit

#6 THHN in other Flex sizes

Other wire sizes in 2" Flex

Charts