ConduitCount

How many #6 THHN fit in 4" Flex?

996 AWG THHN/THWN-2 wires in 4" Flexible metal conduit (FMC, Greenfield)

12.566 sq in × 40 % = 5.0264 sq in allowed. ÷ 0.0507 sq in per wire = 99.14, so 99.

99 #6 THHN in 4" Flex, drawn to scale

This pull in numbers

99 wires fill
39.9 % of 4" Flex
Limit for three or more
40 %
For 100 or more
no bigger Flex
Pipe to wire diameter
15.75 to 1
In THW insulation
69 fit
In XHHW-2 insulation
85 fit

Before you pull 99

#6 THHN in other 4" conduit

ConduitInside areaMost #6 THHN
Electrical metallic tubing14.753116
Intermediate metal conduit13.631107
Rigid metal conduit (RMC, GRC)12.882101
Rigid PVC conduit, Schedule 4012.55499
Rigid PVC conduit, Schedule 8011.25889
Flexible metal conduit (FMC, Greenfield)12.56699
Liquidtight flexible metal conduit (LFMC)12.692100

#6 THHN in other Flex sizes

Other wire sizes in 4" Flex

Charts