ConduitCount

How many #10 THHN fit in 1" Flex?

1510 AWG THHN/THWN-2 wires in 1" Flexible metal conduit (FMC, Greenfield)

0.817 sq in × 40 % = 0.3268 sq in allowed. ÷ 0.0211 sq in per wire = 15.49, so 15.

15 #10 THHN in 1" Flex, drawn to scale

This pull in numbers

15 wires fill
38.7 % of 1" Flex
Limit for three or more
40 %
For 16 or more
1-1/4" Flex, up to 24
Pipe to wire diameter
6.22 to 1
In THW insulation
13 fit
In XHHW-2 insulation
13 fit

Before you pull 15

#10 THHN in other 1" conduit

#10 THHN in other Flex sizes

Other wire sizes in 1" Flex

Charts