How many #8 THHN fit in 1" PVC Sch 40?
98 AWG THHN/THWN-2 wires in 1" Rigid PVC conduit, Schedule 40
0.832 sq in × 40 % = 0.3328 sq in allowed. ÷ 0.0366 sq in per wire = 9.09, so 9.
This pull in numbers
- 9 wires fill
- 39.6 % of 1" PVC Sch 40
- Limit for three or more
- 40 %
- For 10 or more
- 1-1/4" PVC Sch 40, up to 16
- Pipe to wire diameter
- 4.76 to 1
- In THW insulation
- 7 fit
- In XHHW-2 insulation
- 7 fit
Before you pull 9
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 9 is the total, not the hots.
- Derating. If all 9 were current-carrying, each would be adjusted to 70 % of its ampacity (Table 310.15(C)(1)): a #8 THHN at 55 A in the 90 °C column becomes 38.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#8 THHN in other 1" conduit
| Conduit | Inside area | Most #8 THHN |
|---|---|---|
| Electrical metallic tubing | 0.864 | 9 |
| Intermediate metal conduit | 0.959 | 10 |
| Rigid metal conduit (RMC, GRC) | 0.887 | 9 |
| Rigid PVC conduit, Schedule 40 | 0.832 | 9 |
| Rigid PVC conduit, Schedule 80 | 0.688 | 7 |
| Flexible metal conduit (FMC, Greenfield) | 0.817 | 9 |
| Liquidtight flexible metal conduit (LFMC) | 0.873 | 9 |
| Electrical nonmetallic tubing (smurf tube) | 0.832 | 9 |