ConduitCount

How many #12 THHN fit in 1" EMT?

2612 AWG THHN/THWN-2 wires in 1" Electrical metallic tubing

0.864 sq in × 40 % = 0.3456 sq in allowed. ÷ 0.0133 sq in per wire = 25.98, which Note 7 rounds up to 26 because the decimal is 0.8 or more.

26 #12 THHN in 1" EMT, drawn to scale

This pull in numbers

26 wires fill
40.0 % of 1" EMT
Limit for three or more
40 %
For 27 or more
1-1/4" EMT, up to 45
Pipe to wire diameter
8.07 to 1
In THW insulation
19 fit
In XHHW-2 insulation
19 fit

Before you pull 26

#12 THHN in other 1" conduit

#12 THHN in other EMT sizes

Other wire sizes in 1" EMT

Charts