How many #10 THHN fit in 1" EMT?

1610 AWG THHN/THWN-2 wires in 1" Electrical metallic tubing

0.864 sq in × 40 % = 0.3456 sq in allowed. ÷ 0.0211 sq in per wire = 16.38, so 16.

16 #10 THHN in 1" EMT, drawn to scale

This pull in numbers

16 wires fill
39.1 % of 1" EMT
Limit for three or more
40 %
For 17 or more
1-1/4" EMT, up to 28
Pipe to wire diameter
6.40 to 1
In THW insulation
14 fit
In XHHW-2 insulation
14 fit

Before you pull 16

#10 THHN in other 1" conduit

#10 THHN in other EMT sizes

Other wire sizes in 1" EMT

Charts