ConduitCount

2" ENT conduit fill

2" Electrical nonmetallic tubing (smurf tube) has an inside area of 3.291 sq in (2.047 in across). Three or more wires may take 40 % of it: 1.3164 sq in.

One wire, 53 %
1.7442 sq in
Two wires, 31 %
1.0202 sq in
Three or more, 40 %
1.3164 sq in
Nipple, 60 %
1.9746 sq in
36 #8 THHN, the most it may hold, drawn to scale

How many wires fit in 2" ENT

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG1359494
12 AWG997272
10 AWG625454
8 AWG363030
6 AWG262218
4 AWG161613
3 AWG131311
2 AWG111110
1 AWG887
1/0 AWG776
2/0 AWG665
3/0 AWG554
4/0 AWG443
250 kcmil333
300 kcmil331
350 kcmil111
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil111
900 kcmil111
1000 kcmil111

Other 2" conduit

ConduitInside area#14#12#10#8#6
Electrical nonmetallic tubing (smurf tube)3.29113599623626
Electrical metallic tubing3.356138101633626
Intermediate metal conduit3.630149109693928
Rigid metal conduit (RMC, GRC)3.408140102643727
Rigid PVC conduit, Schedule 403.29113599623626
Rigid PVC conduit, Schedule 802.87411886543122
Flexible metal conduit (FMC, Greenfield)3.26913598623525
Liquidtight flexible metal conduit (LFMC)3.24613497613525

About ENT

ENT (smurf tube) is the flexible blue tubing used inside walls and slabs, sold in coils rather than sticks. See strap spacing and the fill rules.