How many 250 kcmil THHN fit in 2" ENT?

3250 kcmil THHN/THWN-2 wires in 2" Electrical nonmetallic tubing (smurf tube)

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.3970 sq in per wire = 3.32, so 3.

3 250 kcmil THHN in 2" ENT, drawn to scale

This pull in numbers

3 wires fill
36.2 % of 2" ENT
Limit for three or more
40 %
For 4 or more
no bigger ENT
Pipe to wire diameter
2.88 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.88 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.