ConduitCount

2" IMC conduit fill

2" Intermediate metal conduit has an inside area of 3.630 sq in (2.150 in across). Three or more wires may take 40 % of it: 1.4520 sq in.

One wire, 53 %
1.9239 sq in
Two wires, 31 %
1.1253 sq in
Three or more, 40 %
1.4520 sq in
Nipple, 60 %
2.1780 sq in
Support
Every 10 ft, 3 ft from boxes
Sold in
10 ft sticks
39 #8 THHN, the most it may hold, drawn to scale

How many wires fit in 2" IMC

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG149104104
12 AWG1098080
10 AWG695959
8 AWG393333
6 AWG282420
4 AWG171815
3 AWG151513
2 AWG121211
1 AWG997
1/0 AWG886
2/0 AWG665
3/0 AWG554
4/0 AWG444
250 kcmil333
300 kcmil332
350 kcmil231
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil111
900 kcmil111
1000 kcmil111

Other 2" conduit

ConduitInside area#14#12#10#8#6
Intermediate metal conduit3.630149109693928
Electrical metallic tubing3.356138101633626
Rigid metal conduit (RMC, GRC)3.408140102643727
Rigid PVC conduit, Schedule 403.29113599623626
Rigid PVC conduit, Schedule 802.87411886543122
Flexible metal conduit (FMC, Greenfield)3.26913598623525
Liquidtight flexible metal conduit (LFMC)3.24613497613525
Electrical nonmetallic tubing (smurf tube)3.29113599623626

About IMC

IMC has a thinner wall than rigid, so it has a little more room inside size for size. Support follows 342.30: within 3 ft of each box, then every 10 ft, or longer on straight runs with threaded couplings. See strap spacing and the fill rules.