9912 AWG THHN/THWN-2 wires in 2" Electrical nonmetallic tubing (smurf tube)

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.0133 sq in per wire = 98.98, which Note 7 rounds up to 99 because the decimal is 0.8 or more.

99 #12 THHN in 2" ENT, drawn to scale

This pull in numbers

99 wires fill
40.0 % of 2" ENT
Limit for three or more
40 %
For 100 or more
no bigger ENT
Pipe to wire diameter
15.75 to 1
In THW insulation
72 fit
In XHHW-2 insulation
72 fit

Before you pull 99

#12 THHN in other 2" conduit

#12 THHN in other ENT sizes

Other wire sizes in 2" ENT