How many #10 THHN fit in 2" ENT?
6210 AWG THHN/THWN-2 wires in 2" Electrical nonmetallic tubing (smurf tube)
3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.0211 sq in per wire = 62.39, so 62.
This pull in numbers
- 62 wires fill
- 39.8 % of 2" ENT
- Limit for three or more
- 40 %
- For 63 or more
- no bigger ENT
- Pipe to wire diameter
- 12.48 to 1
- In THW insulation
- 54 fit
- In XHHW-2 insulation
- 54 fit
Before you pull 62
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 62 is the total, not the hots.
- Derating. If all 62 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #10 THHN at 40 A in the 90 °C column becomes 14 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#10 THHN in other 2" conduit
| Conduit | Inside area | Most #10 THHN |
|---|---|---|
| Electrical metallic tubing | 3.356 | 63 |
| Intermediate metal conduit | 3.630 | 69 |
| Rigid metal conduit (RMC, GRC) | 3.408 | 64 |
| Rigid PVC conduit, Schedule 40 | 3.291 | 62 |
| Rigid PVC conduit, Schedule 80 | 2.874 | 54 |
| Flexible metal conduit (FMC, Greenfield) | 3.269 | 62 |
| Liquidtight flexible metal conduit (LFMC) | 3.246 | 61 |
| Electrical nonmetallic tubing (smurf tube) | 3.291 | 62 |
#10 THHN in other ENT sizes
Other wire sizes in 2" ENT
#14: 135#12: 99#10: 62#8: 36#6: 26#4: 16#3: 13#2: 11#1: 8#1/0: 7#2/0: 6#3/0: 5#4/0: 4250 kcmil: 3300 kcmil: 3350 kcmil: 1500 kcmil: 1