ConduitCount

2" PVC Sch 80 conduit fill

2" Rigid PVC conduit, Schedule 80 has an inside area of 2.874 sq in (1.913 in across). Three or more wires may take 40 % of it: 1.1496 sq in.

One wire, 53 %
1.5232 sq in
Two wires, 31 %
0.8909 sq in
Three or more, 40 %
1.1496 sq in
Nipple, 60 %
1.7244 sq in
Support
Every 5 ft, 3 ft from boxes
Sold in
10 ft sticks
54 #10 THHN, the most it may hold, drawn to scale

How many wires fit in 2" PVC Sch 80

All wires the same size and type, by Annex C's method. For a mix of sizes, open the calculator.

Wire sizeTHHN/THWN-2XHHW-2THW/THW-2
14 AWG1188282
12 AWG866363
10 AWG544747
8 AWG312626
6 AWG221916
4 AWG141412
3 AWG121210
2 AWG10108
1 AWG776
1/0 AWG665
2/0 AWG554
3/0 AWG443
4/0 AWG333
250 kcmil331
300 kcmil111
350 kcmil111
400 kcmil111
500 kcmil111
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil111
900 kcmil111
1000 kcmil111

Other 2" conduit

ConduitInside area#14#12#10#8#6
Rigid PVC conduit, Schedule 802.87411886543122
Electrical metallic tubing3.356138101633626
Intermediate metal conduit3.630149109693928
Rigid metal conduit (RMC, GRC)3.408140102643727
Rigid PVC conduit, Schedule 403.29113599623626
Flexible metal conduit (FMC, Greenfield)3.26913598623525
Liquidtight flexible metal conduit (LFMC)3.24613497613525
Electrical nonmetallic tubing (smurf tube)3.29113599623626

About PVC Sch 80

Schedule 80 has a thicker wall for where it can be hit, so it holds fewer wires than Schedule 40 of the same trade size. Support is the same as Schedule 40 (Table 352.30). See strap spacing and the fill rules.