ConduitCount

How many #6 THHN fit in 3/4" ENT?

46 AWG THHN/THWN-2 wires in 3/4" Electrical nonmetallic tubing (smurf tube)

0.508 sq in × 40 % = 0.2032 sq in allowed. ÷ 0.0507 sq in per wire = 4.01, so 4.

4 #6 THHN in 3/4" ENT, drawn to scale

This pull in numbers

4 wires fill
39.9 % of 3/4" ENT
Limit for three or more
40 %
For 5 or more
1" ENT, up to 6
Pipe to wire diameter
3.17 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

The pipe is 3.17 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 4

#6 THHN in other 3/4" conduit

#6 THHN in other ENT sizes

Other wire sizes in 3/4" ENT

Charts