ConduitCount

How many #12 THHN fit in 3/4" ENT?

1512 AWG THHN/THWN-2 wires in 3/4" Electrical nonmetallic tubing (smurf tube)

0.508 sq in × 40 % = 0.2032 sq in allowed. ÷ 0.0133 sq in per wire = 15.28, so 15.

15 #12 THHN in 3/4" ENT, drawn to scale

This pull in numbers

15 wires fill
39.3 % of 3/4" ENT
Limit for three or more
40 %
For 16 or more
1" ENT, up to 25
Pipe to wire diameter
6.18 to 1
In THW insulation
11 fit
In XHHW-2 insulation
11 fit

Before you pull 15

#12 THHN in other 3/4" conduit

#12 THHN in other ENT sizes

Other wire sizes in 3/4" ENT

Charts