ConduitCount

How many #10 THHN fit in 2-1/2" Liquidtight?

9210 AWG THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.0211 sq in per wire = 92.53, so 92.

92 #10 THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

92 wires fill
39.8 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 93 or more
3" Liquidtight, up to 141
Pipe to wire diameter
15.20 to 1
In THW insulation
80 fit
In XHHW-2 insulation
80 fit

Before you pull 92

#10 THHN in other 2-1/2" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing5.858111
Intermediate metal conduit5.13597
Rigid metal conduit (RMC, GRC)4.86692
Rigid PVC conduit, Schedule 404.69589
Rigid PVC conduit, Schedule 804.11978
Flexible metal conduit (FMC, Greenfield)4.90993
Liquidtight flexible metal conduit (LFMC)4.88192

#10 THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts