ConduitCount

How many #10 THHN fit in 2" Liquidtight?

6110 AWG THHN/THWN-2 wires in 2" Liquidtight flexible metal conduit (LFMC)

3.246 sq in × 40 % = 1.2984 sq in allowed. ÷ 0.0211 sq in per wire = 61.54, so 61.

61 #10 THHN in 2" Liquidtight, drawn to scale

This pull in numbers

61 wires fill
39.7 % of 2" Liquidtight
Limit for three or more
40 %
For 62 or more
2-1/2" Liquidtight, up to 92
Pipe to wire diameter
12.40 to 1
In THW insulation
53 fit
In XHHW-2 insulation
53 fit

Before you pull 61

#10 THHN in other 2" conduit

#10 THHN in other Liquidtight sizes

Other wire sizes in 2" Liquidtight

Charts