ConduitCount

How many #12 THHN fit in 2-1/2" EMT?

17612 AWG THHN/THWN-2 wires in 2-1/2" Electrical metallic tubing

5.858 sq in × 40 % = 2.3432 sq in allowed. ÷ 0.0133 sq in per wire = 176.18, so 176.

176 #12 THHN in 2-1/2" EMT, drawn to scale

This pull in numbers

176 wires fill
40.0 % of 2-1/2" EMT
Limit for three or more
40 %
For 177 or more
3" EMT, up to 266
Pipe to wire diameter
21.01 to 1
In THW insulation
129 fit
In XHHW-2 insulation
129 fit

Before you pull 176

#12 THHN in other 2-1/2" conduit

#12 THHN in other EMT sizes

Other wire sizes in 2-1/2" EMT

Charts