ConduitCount

How many #12 THHN fit in 3/4" EMT?

1612 AWG THHN/THWN-2 wires in 3/4" Electrical metallic tubing

0.533 sq in × 40 % = 0.2132 sq in allowed. ÷ 0.0133 sq in per wire = 16.03, so 16.

16 #12 THHN in 3/4" EMT, drawn to scale

This pull in numbers

16 wires fill
39.9 % of 3/4" EMT
Limit for three or more
40 %
For 17 or more
1" EMT, up to 26
Pipe to wire diameter
6.34 to 1
In THW insulation
11 fit
In XHHW-2 insulation
11 fit

Before you pull 16

#12 THHN in other 3/4" conduit

#12 THHN in other EMT sizes

Other wire sizes in 3/4" EMT

Charts