ConduitCount

How many #12 THHN fit in 2" EMT?

10112 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.0133 sq in per wire = 100.93, which Note 7 rounds up to 101 because the decimal is 0.8 or more.

101 #12 THHN in 2" EMT, drawn to scale

This pull in numbers

101 wires fill
40.0 % of 2" EMT
Limit for three or more
40 %
For 102 or more
2-1/2" EMT, up to 176
Pipe to wire diameter
15.90 to 1
In THW insulation
74 fit
In XHHW-2 insulation
74 fit

Before you pull 101

#12 THHN in other 2" conduit

#12 THHN in other EMT sizes

Other wire sizes in 2" EMT

Charts