ConduitCount

How many #12 THHN fit in 3/4" Rigid?

1612 AWG THHN/THWN-2 wires in 3/4" Rigid metal conduit (RMC, GRC)

0.549 sq in × 40 % = 0.2196 sq in allowed. ÷ 0.0133 sq in per wire = 16.51, so 16.

16 #12 THHN in 3/4" Rigid, drawn to scale

This pull in numbers

16 wires fill
38.8 % of 3/4" Rigid
Limit for three or more
40 %
For 17 or more
1" Rigid, up to 26
Pipe to wire diameter
6.43 to 1
In THW insulation
12 fit
In XHHW-2 insulation
12 fit

Before you pull 16

#12 THHN in other 3/4" conduit

#12 THHN in other Rigid sizes

Other wire sizes in 3/4" Rigid

Charts