ConduitCount

How many #14 THHN fit in 3/4" EMT?

2214 AWG THHN/THWN-2 wires in 3/4" Electrical metallic tubing

0.533 sq in × 40 % = 0.2132 sq in allowed. ÷ 0.0097 sq in per wire = 21.98, which Note 7 rounds up to 22 because the decimal is 0.8 or more.

22 #14 THHN in 3/4" EMT, drawn to scale

This pull in numbers

22 wires fill
40.0 % of 3/4" EMT
Limit for three or more
40 %
For 23 or more
1" EMT, up to 35
Pipe to wire diameter
7.42 to 1
In THW insulation
15 fit
In XHHW-2 insulation
15 fit

Before you pull 22

#14 THHN in other 3/4" conduit

#14 THHN in other EMT sizes

Other wire sizes in 3/4" EMT

Charts