ConduitCount

How many #14 THHN fit in 1-1/2" EMT?

8414 AWG THHN/THWN-2 wires in 1-1/2" Electrical metallic tubing

2.036 sq in × 40 % = 0.8144 sq in allowed. ÷ 0.0097 sq in per wire = 83.96, which Note 7 rounds up to 84 because the decimal is 0.8 or more.

84 #14 THHN in 1-1/2" EMT, drawn to scale

This pull in numbers

84 wires fill
40.0 % of 1-1/2" EMT
Limit for three or more
40 %
For 85 or more
2" EMT, up to 138
Pipe to wire diameter
14.50 to 1
In THW insulation
58 fit
In XHHW-2 insulation
58 fit

Before you pull 84

#14 THHN in other 1-1/2" conduit

#14 THHN in other EMT sizes

Other wire sizes in 1-1/2" EMT

Charts