ConduitCount

How many #4 THHN fit in 3/4" EMT?

24 AWG THHN/THWN-2 wires in 3/4" Electrical metallic tubing

0.533 sq in × 31 % = 0.1652 sq in allowed. ÷ 0.0824 sq in per wire = 2.01.

2 #4 THHN in 3/4" EMT, drawn to scale

This pull in numbers

2 wires fill
30.9 % of 3/4" EMT
Limit for two
31 %
For 3 or more
1" EMT, up to 4
Pipe to wire diameter
2.54 to 1
In THW insulation
1 fit
In XHHW-2 insulation
2 fit

Before you pull 2

#4 THHN in other 3/4" conduit

#4 THHN in other EMT sizes

Other wire sizes in 3/4" EMT

Charts