ConduitCount

How many #1/0 THHN fit in 3/4" EMT?

11/0 AWG THHN/THWN-2 wires in 3/4" Electrical metallic tubing

0.533 sq in × 53 % = 0.2825 sq in allowed. ÷ 0.1855 sq in per wire = 1.52.

1 #1/0 THHN in 3/4" EMT, drawn to scale

This pull in numbers

1 wires fill
34.8 % of 3/4" EMT
Limit for one
53 %
For 2 or more
1-1/4" EMT, up to 3
Pipe to wire diameter
1.70 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#1/0 THHN in other 3/4" conduit

#1/0 THHN in other EMT sizes

Other wire sizes in 3/4" EMT

Charts