How many 250 kcmil THHN fit in 2" Rigid?

3250 kcmil THHN/THWN-2 wires in 2" Rigid metal conduit (RMC, GRC)

3.408 sq in × 40 % = 1.3632 sq in allowed. ÷ 0.3970 sq in per wire = 3.43, so 3.

3 250 kcmil THHN in 2" Rigid, drawn to scale

This pull in numbers

3 wires fill
34.9 % of 2" Rigid
Limit for three or more
40 %
For 4 or more
2-1/2" Rigid, up to 5
Pipe to wire diameter
2.93 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.93 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.