ConduitCount

How many #3 THHN fit in 2" Liquidtight?

133 AWG THHN/THWN-2 wires in 2" Liquidtight flexible metal conduit (LFMC)

3.246 sq in × 40 % = 1.2984 sq in allowed. ÷ 0.0973 sq in per wire = 13.34, so 13.

13 #3 THHN in 2" Liquidtight, drawn to scale

This pull in numbers

13 wires fill
39.0 % of 2" Liquidtight
Limit for three or more
40 %
For 14 or more
2-1/2" Liquidtight, up to 20
Pipe to wire diameter
5.78 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 13

#3 THHN in other 2" conduit

#3 THHN in other Liquidtight sizes

Other wire sizes in 2" Liquidtight

Charts