ConduitCount

How many #1 THHN fit in 2" Liquidtight?

81 AWG THHN/THWN-2 wires in 2" Liquidtight flexible metal conduit (LFMC)

3.246 sq in × 40 % = 1.2984 sq in allowed. ÷ 0.1562 sq in per wire = 8.31, so 8.

8 #1 THHN in 2" Liquidtight, drawn to scale

This pull in numbers

8 wires fill
38.5 % of 2" Liquidtight
Limit for three or more
40 %
For 9 or more
2-1/2" Liquidtight, up to 12
Pipe to wire diameter
4.56 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#1 THHN in other 2" conduit

#1 THHN in other Liquidtight sizes

Other wire sizes in 2" Liquidtight

Charts