33 AWG THHN/THWN-2 wires in 1" Rigid PVC conduit, Schedule 40

0.832 sq in × 40 % = 0.3328 sq in allowed. ÷ 0.0973 sq in per wire = 3.42, so 3.

3 #3 THHN in 1" PVC Sch 40, drawn to scale

This pull in numbers

3 wires fill
35.1 % of 1" PVC Sch 40
Limit for three or more
40 %
For 4 or more
1-1/4" PVC Sch 40, up to 6
Pipe to wire diameter
2.92 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.92 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.