ConduitCount

How many 250 kcmil THHN fit in 1" PVC Sch 40?

1250 kcmil THHN/THWN-2 wires in 1" Rigid PVC conduit, Schedule 40

0.832 sq in × 53 % = 0.4410 sq in allowed. ÷ 0.3970 sq in per wire = 1.11.

1 250 kcmil THHN in 1" PVC Sch 40, drawn to scale

This pull in numbers

1 wires fill
47.7 % of 1" PVC Sch 40
Limit for one
53 %
For 2 or more
2" PVC Sch 40, up to 3
Pipe to wire diameter
1.45 to 1
In THW insulation
0 fit
In XHHW-2 insulation
1 fit

Before you pull 1

250 kcmil THHN in other 1" conduit

ConduitInside areaMost 250 kcmil THHN
Electrical metallic tubing0.8641
Intermediate metal conduit0.9591
Rigid metal conduit (RMC, GRC)0.8871
Rigid PVC conduit, Schedule 400.8321
Rigid PVC conduit, Schedule 800.6880
Flexible metal conduit (FMC, Greenfield)0.8171
Liquidtight flexible metal conduit (LFMC)0.8731
Electrical nonmetallic tubing (smurf tube)0.8321

250 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 1" PVC Sch 40

Charts